Heat-exchanger effectiveness and finite capacity rates

Derive the counterflow effectiveness relation and determine outlet temperatures when neither stream temperature is fixed.

From first principles

Derive exchanger effectiveness from the limiting heat balance

Consider a steady two-stream heat exchanger with no external heat gain, constant specific heats and no phase change. Each stream has a capacity rate \(C=\dot m c_p\), the power required for one kelvin of temperature change. Applying the first law independently to each stream gives a common transferred heat rate

\[\dot Q=C_h(T_{h,i}-T_{h,o})=C_c(T_{c,o}-T_{c,i}).\]

In passive exchange neither exit can cross the opposite stream’s inlet temperature. Therefore the maximum available temperature change on either stream is bounded by the same inlet difference \(T_{h,i}-T_{c,i}\). The smaller capacity rate limits the largest conceivable common duty. Define effectiveness from this physically accessible upper scale:

\[\dot Q_{\max}=C_{\min}(T_{h,i}-T_{c,i}),\]
\[\varepsilon=\dot Q/\dot Q_{\max},\]
\[\mathrm{NTU}=UA/C_{\min}.\]

The bound need not be reached by a finite exchanger or by every flow arrangement. Local conductance \(U\,dA\) and the changing local temperature difference determine the actual effectiveness. Knowing the two capacity rates and \(\varepsilon\) suffices to reconstruct both outlet temperatures using the separate energy balances.

Background · Heat-exchanger effectiveness
\[\epsilon=\dot Q/[C_{\min}(T_{h,i}-T_{c,i})]\]

Heat-capacity rate is mass flow times specific heat for a single-phase stream. The smaller rate limits the maximum possible sensible heat transfer.

Hot and cold temperatures both fall along a coordinate measured from the hot inlet. The two fluids travel in opposite directions and stay twenty kelvin apart.Open full-size diagram
Read exchanger terminal temperatures at the same physical end The hot stream enters at 80 °C and leaves at 50 °C. The cold stream enters at 30 °C on the right and leaves at 60 °C on the left. Equal heat-capacity rates and uniform conductance per length give parallel lines. The local driving difference is 20 K throughout, even though the cold outlet is hotter than the hot outlet.

Derivation and applications

Where the logarithmic mean temperature difference comes from

A local heat-transfer coefficient multiplies the temperature difference at that location. Integrating one exchanger therefore requires the changing driving difference across its whole area. Take a steady counterflow exchanger with no phase change, constant positive capacity rates \(C_h=\dot m_h c_h\), \(C_c=\dot m_c c_c\), constant overall coefficient \(U\) and no external heat loss. Measure area coordinate \(A'\) along the hot flow. Let \(d\dot Q\) be the positive heat transfer from hot to cold over the increment. Both fluid temperatures decrease along this chosen coordinate because the cold stream flows the other way.

\[d\dot Q=U(T_h-T_c)\,dA',\]
\[dT_h=-d\dot Q/C_h,\]
\[dT_c=-d\dot Q/C_c .\]

Thus \(\Delta=T_h-T_c\) changes linearly with cumulative heat transfer. Write its two physical terminal values as \(\Delta_1=T_{h,i}-T_{c,o}\) and \(\Delta_2=T_{h,o}-T_{c,i}\):

\[d\Delta=(1/C_c-1/C_h)d\dot Q,\]
\[\Delta_2-\Delta_1=(1/C_c-1/C_h)\dot Q .\]

To recover total area, integrate \(dA'=d\dot Q/(U\Delta)\) using the preceding linear relation. Eliminating the reciprocal capacity difference leaves

\[\dot Q=UA\,\frac{\Delta_1-\Delta_2}{\ln(\Delta_1/\Delta_2)} .\]

For equal terminal differences the apparent zero divided by zero has limit \(\Delta_1\). When one positive approach tends toward zero at a fixed heat duty, the necessary area diverges. Terminal differences must pair the temperatures at the same physical end, not two inlet temperatures chosen from opposite ends.

Worked example

Size an exchanger from measured terminal temperatures

A hot stream cools from \(90\) to \(55^\circ\)C while the counterflow cold stream warms from \(20\) to \(60^\circ\)C. The terminal differences are \(30\) and \(35\) K, so their logarithmic mean is

\[5/\ln(35/30)=32.4\,\mathrm{K}.\]

For a duty of \(70.0\) kW and \(U=500\) W/(m² K), the required area is \(4.32\) m². The capacities \(2.00\) and \(1.75\) kW/K independently deliver the same \(70.0\) kW.

Second application

Compare equal duty at a tighter terminal approach

A redesign has measured terminal differences of \(5.00\) and \(35.0\) K at the same duty and coefficient. The logarithmic mean drops to \(30/\ln7=15.4\) K and the required area rises to \(9.08\) m². Using the arithmetic mean \(20.0\) K would give only \(7.00\) m². The region with low driving difference consumes disproportionately more area per kilowatt transferred.

Try it · Lmtd area

Set the inputs to the values in the worked example, then vary one quantity while holding the others fixed. Compare the curve and numerical balance with the second application. The calculation uses the assumptions derived above; its readout identifies bounds such as choking, phase-region changes and inconsistent measurements.

OneSimulation laboratory

Explain why greater exchanger effectiveness can give less power

Start from this chapter. Predict outlet temperatures using the counterflow effectiveness relation. At fixed conductance, increasing NTU here reduces the smaller heat-capacity rate. Determine whether effectiveness and total power move together.

Compare recorded OneSimulation runs on this page. To test your own inputs, download the notebook and model files and run the model in an activated OneSimulation environment.

Run the heat-exchanger example at ntu=1.5, capacity_ratio=0.6 and inlet temperatures 350 and 290 K. Record both cross-section-averaged outlet temperatures and the power lost by the hot stream. In this code the geometry and conductance are fixed. Changing ntu changes the computed capacity rates and inlet speeds.

  1. Set ntu=3.0 at the original capacity ratio. Both flows halve. The one-dimensional model predicts an effectiveness of 0.853 and a hot outlet near 298.8 K. The heat rate should fall, despite the greater effectiveness, since there is now less hot water to cool every second.
  2. Restore ntu=1.5 and set capacity_ratio=0.3. The hot capacity stays fixed and the cold capacity doubles. Expect a lower cold outlet (about 303.1 K) and an increased heat rate (about 0.235 W). Check both energy balances against the numerical solution.
Computed exchanger outlets and heat released by the hot stream
NTU and capacity ratioHot outlet (K)Cold outlet (K)Heat rate (W)
1.5, ratio 0.60309.84314.200.2168
3.0, ratio 0.60299.36320.790.1367
1.5, ratio 0.30306.62303.110.2343
Doubling NTU here lowers transferred heat from 0.2168 to 0.1367 W because the capacity rates fall. Lowering only the capacity ratio at the original NTU increases the heat rate.
Doubling NTU here lowers transferred heat from 0.2168 to 0.1367 W because the capacity rates fall. Lowering only the capacity ratio at the original NTU increases the heat rate.

As a numerical balance check, also calculate the heat gained by the cold stream. The two outlet-based estimates differ by about 0.5% in the baseline and 1.4% at NTU 3. Refining the mesh lets you test how much of this discrepancy comes from the spatial approximation.

View the OneSimulation counterflow model and its temperature profiles.

Download experiment files (ZIP) Extract the files together and open counterflow_heat_exchanger_ntu.ipynb in a local OneSimulation environment.

Interactive reference for the OneSimulation laboratory

Change capacity rates through NTU at fixed conductance and check both outlet temperatures. The browser evaluates the1D counterflow energy-balance reference.

Problem sheet 6 · Recover an exchanger capacity rate from outlet data

Read the model setup and preparatory problems

Set the maximum possible heat rate

In a two-stream heat exchanger, the hot temperature falls as the cold temperature rises. Treat each stream as single phase with constant heat capacity rate \(C=\dot m c_p\) in watts per kelvin. Neglect heat leakage, axial conduction and changes in kinetic energy. A steady overall balance gives

\[Q=C_h(T_{hi}-T_{ho})=C_c(T_{co}-T_{ci}).\]

Performing this balance alone leaves both outlet temperatures and the transferred heat rate unknown.

The stream with smaller capacity rate would undergo the larger temperature change for a given heat rate. Even in an ideal counterflow exchanger it cannot pass the inlet temperature of the other stream at its nearest end. Thus \(Q_{\max}=C_{\min}(T_{hi}-T_{ci})\). Effectiveness is \(\varepsilon=Q/Q_{\max}\), which immediately gives both outlet temperatures once the heat transfer law fixes \(\varepsilon\).

Apply a balance to an area element

Let \(A\) increase along the hot stream and write the local temperature difference \(\Delta=T_h-T_c\). An element transfers \(dQ=U\Delta\,dA\). In counterflow both temperature profiles decrease when followed in the hot-stream direction, giving \(dT_h=-dQ/C_h\), \(dT_c=-dQ/C_c\). Hence \(d\ln\Delta/dA=U(1/C_c-1/C_h)\). Integrate over area and express each end difference in terms of inlet temperatures and total heat rate using the stream balances.

\[NTU=UA/C_{\min},\]
\[C_r=C_{\min}/C_{\max},\]
\[\varepsilon=\frac{1-\exp[-NTU(1-C_r)]}{1-C_r\exp[-NTU(1-C_r)]}.\]

The sign in the differential balance follows from the chosen spatial direction. In parallel flow the cold stream warms along that coordinate and the local temperature difference decays more rapidly. For equal capacity rates the counterflow formula has a removable zero over zero. Its limit is \(NTU/(1+NTU)\), which can also be obtained from the constant temperature difference in that special case.

OneSimulation · Can the cold outlet leave hotter than the hot outlet?

The hot stream enters at 80 °C with a heat-capacity rate of 2 kW/K. The cold stream enters at 20 °C with a capacity rate of 1 kW/K. Compare the same heat exchanger conductance in parallel flow and counterflow. Obtain the two discharges from the same transferred heat rate \(\dot Q\), using \(\dot C=\dot m c_p\).

\[T_{h,o}=T_{h,i}-\dot Q/\dot C_h,\]
\[T_{c,o}=T_{c,i}+\dot Q/\dot C_c.\]

Equal outlets occur at 60 °C and require 40 kW, or effectiveness \(2/3\). Parallel flow approaches this common temperature asymptotically. Counterflow reaches it at \(\mathrm{NTU}=2\ln2\). At NTU 2 the two OneSimulation models predict cold and hot outlets of 66.5 °C and 56.8 °C in counterflow, against 58.0 °C and 61.0 °C in parallel flow. The counterflow outlets sit at opposite ends; heat still travels locally from the hotter fluid to the colder one.

"""Check for an outlet temperature cross in a two-stream heat exchanger."""
import matplotlib.pyplot as plt
import numpy as np
from onesim.physics.systems.process import counterflow_effectiveness, parallel_flow_effectiveness

hot_in, cold_in = 80., 20.       # °C
hot_rate, cold_rate = 2., 1.     # kW/K
capacity_min = min(hot_rate, cold_rate)
ratio = capacity_min/max(hot_rate, cold_rate)
ntu = np.linspace(0, 4, 201)

fig, ax = plt.subplots(figsize=(7, 4), constrained_layout=True)
for name, model, style in [("Counterflow", counterflow_effectiveness, "-"),
                            ("Parallel flow", parallel_flow_effectiveness, "--")]:
    heat = model(ntu, ratio)*capacity_min*(hot_in-cold_in)  # kW
    hot_out = hot_in - heat/hot_rate
    cold_out = cold_in + heat/cold_rate
    assert np.allclose(hot_rate*(hot_in-hot_out), cold_rate*(cold_out-cold_in))
    ax.plot(ntu, hot_out, style, color="#a5442e", label=f"{name}, hot outlet")
    ax.plot(ntu, cold_out, style, color="#19596a", label=f"{name}, cold outlet")

ax.axvline(2*np.log(2), color="0.5", linestyle=":", label="Counterflow outlets equal")
ax.set(xlabel="Transfer units UA / minimum capacity rate", ylabel="Outlet temperature (°C)")
ax.legend(fontsize=8)
fig.savefig("engineering-thermodynamics.png", dpi=170)
Solid counterflow outlet temperature curves cross; dashed parallel-flow outlet temperatures approach a common limit from either side.
Compare outlets at the same horizontal coordinate. A temperature cross in counterflow describes two different positions along the exchanger.

Download the Python example

Change the inputs of this exact example and compare the recalculated curves with the recorded OneSimulation output above. The browser evaluates the stated analytical or modal reference.

Predict both outlet temperatures

A counterflow cooler receives a hot stream at 90 °C with \(C_h=2.0\,\mathrm{kW/K}\) and a cold stream at 20 °C with \(C_c=1.0\,\mathrm{kW/K}\). Its conductance \(UA\) is 1.50 kW/K. Thus \(C_r=0.5\), \(NTU=1.5\), and the exponential is

\[e^{-0.75}=0.4724.\]

Effectiveness is 0.6908. Consequently \(Q=0.6908(1.0)(90-20)=48.4\,\mathrm{kW}\),

\[T_{ho}=90-48.4/2=65.8^\circ\mathrm C,\]
\[T_{co}=20+48.4=68.4^\circ\mathrm C.\]

The cold outlet is warmer than the hot outlet. They are at opposite physical ends, so this does not imply a local reversal of heat flow. The end differences are \(90-68.4=21.6\) K and \(65.8-20=45.8\) K, both positive. Their logarithmic mean is approximately \((45.8-21.6)/\ln(45.8/21.6)=32.2\,\mathrm K\), independently recovering \(Q=UA\Delta T_{\rm lm}\simeq48.3\,\mathrm{kW}\). This local check catches errors caused by swapping the terminal temperatures of a counterflow exchanger.

Predict the counterflow experiment

A smaller stream capacity rate raises NTU when the exchanger conductance is held fixed, yet it can reduce heat transfer in watts because less thermal capacity passes each second. For inlet temperatures 350 and 290 K and \(C_r=0.60\), use the counterflow expression to predict the effectiveness at NTU 1.5 and 3.0. Then halve both capacity rates, as the model does to obtain the second NTU, and predict the ratio of heat rates. Check both outlet temperatures and the hot-stream heat rate, paying attention to which stream has the smaller capacity. Open the heat-exchanger experiment.

Identify which side controls an exchanger’s conductance

The effectiveness relation uses a single conductance \(UA\), but a designer may need to determine whether the hot film, cold film or fouling dominates it. Write the total thermal resistance in K/W as \(R_{\rm tot}=1/(h_hA_h)+R_w+R_f+1/(h_cA_c)\). Areas must be kept explicit if the two sides use different reference areas. Suppose a test can vary hot-side flow while holding cold-side flow, wall resistance and deposit condition fixed. Let a supported correlation in the tested region imply \(h_h\propto\dot m_h^{\,n}\). With \(m_r=\dot m_h/\dot m_{\rm ref}\), the relation takes the linear form

\[(UA)^{-1}=R_{\rm fixed}+R_{h,\rm ref}\,m_r^{-n}.\]

This is the basis of a Wilson-plot style separation. Each measured \(UA\) can be obtained from balanced heat duty and the correct logarithmic mean temperature difference. The intercept estimates the combined fixed resistance; the slope estimates the hot-film resistance at reference flow. One set of measurements alone does not separate cold film from wall and deposits individually. Temperature-dependent material properties and changes in the opposite stream can spoil the assumed linear relation.

Treating \(UA\) as proportional to flow whenever convection rises would ignore the series resistances left in its path. As \(m_r\) becomes large the hot-film term tends to zero, leaving an asymptote \(1/R_{\rm fixed}\) rather than unbounded conductance. Pumping power typically rises over this same change of flow.

Use a flow sweep to distinguish fouling from film resistance

A clean counterflow rig at reference hot-side mass flow has \(UA=500\,\mathrm{W/K}\), giving total resistance \(0.00200\,\mathrm{K/W}\). At twice the flow it has \(UA=600\,\mathrm{W/K}\), or \(0.001667\,\mathrm{K/W}\). Over this interval use measured exponent \(n=0.80\), so

\[2^{-0.8}=0.5743.\]

Subtracting the two equations gives

\[R_{h,\rm ref}=(0.00200-0.001667)/(1-0.5743)=0.000783\,\mathrm{K/W}.\]

The combined fixed resistance is \(0.001217\,\mathrm{K/W}\). Even an ideal hot film could raise conductance only to about 822 W/K under the unchanged fixed-side assumptions.

A later test at reference flow gives \(UA=400\,\mathrm{W/K}\), so total resistance has grown to 0.00250 K/W. If a second flow sweep confirms the same hot-film slope, the added fixed resistance is 0.00050 K/W. For a heat-transfer area of 2.0 m² on the chosen basis this corresponds to fouling resistance \(R_f''=0.0010\,\mathrm{m^2K/W}\). If instead the slope has changed, assigning the entire difference to deposits is unwarranted; changed flow distribution or fluid properties may contribute. Temperature measurement also matters strongly when the two terminal differences are close to sensor uncertainty. Compare the hot and cold enthalpy duties before fitting the conductance and retain the residual across all measured flow settings.

A third clean test can challenge the fitted exponent. At four times reference hot flow, the predicted resistance is \(0.001217+0.000783(4^{-0.8})=0.001475\,\mathrm{K/W}\), or \(UA\simeq678\,\mathrm{W/K}\). A systematic departure that grows at high flow could reflect changing cold-side properties, thermocouple bias or failure of the hot-film correlation. Two calibration points always fit a two-parameter straight line; the independent third point actually tests the assumed dependence.

Determine whether a specified exchanger effectiveness is attainable

Fix both inlet temperatures and \(C_{\min}\). Changing area changes NTU. For constant properties and no losses the effectiveness divides actual heat rate by \(C_{\min}(T_{h,i}-T_{c,i})\). Compare two flow arrangements and the isothermal-stream limit.

Determine whether a specified exchanger effectiveness is attainable. Horizontal axis: Number of transfer units, UA/Cmin. Vertical axis: Heat-exchanger effectiveness. Data follow the figure.
With capacity ratio 0.6, parallel flow approaches only 1/1.6 = 0.625 however large the area. Counterflow can exceed 0.8. An area calculation that ignores the arrangement can return a target that the selected exchanger cannot reach.
Read values from the plot
Heat-exchanger effectiveness at selected values of Number of transfer units, UA/Cmin.
Number of transfer units, UA/CminCounterflow, Cr = 0.6Parallel flow, Cr = 0.6Phase-changing stream, Cr = 0
0000
1.240.616170.539050.71062
2.50.811170.613550.91792
3.760.897430.623480.97672
50.941080.624790.99326

Download all 251 plotted samples (CSV)

Interactive calculation · change the inputs of this example

Move the capacity-rate ratio toward one and compare the finite-area behaviour with the phase-change limit.

The curves below are recalculated from this section’s equations in your browser. The fixed reference plot above remains available for comparison.

Study the full derivation

How a gravity-drained condensate film limits heat transfer · Thermal processes and transport in engineering

Saturated vapour condenses on a cool vertical plate. A liquid film thickens as it drains, adding thermal resistance toward the bottom. Derive the local heat-transfer coefficient from coupled momentum and energy balances, then determine which observations would invalidate the smooth-film model.