From first principles
Obtain humidity ratio from partial pressures and dry-air mass
Treat moist air as an ideal mixture of dry air and water vapour occupying the same volume \(V\) at temperature \(T\). Dalton's law gives total pressure \(p=p_{da}+p_v\). For each component \(m_i=p_iV/(R_iT)\), so dividing vapour mass by dry-air mass cancels the shared volume and temperature:
Relative humidity is a different observable. It compares actual vapour partial pressure with the saturation pressure at the same temperature. Cooling without water removal keeps \(\omega\) constant, and approximately constant total pressure then keeps \(p_v\) constant until the saturation curve reaches it:
Below the dew point some water can leave the gas as liquid, while dry-air mass is conserved. A steady coil receiving humidity ratio \(\omega_i\) and delivering \(\omega_o\) therefore removes condensate at rate \(\dot m_{da}(\omega_i-\omega_o)\). Inferring the same removal from relative humidity alone would ignore its dependence on temperature.
Derivation and applications
Measure the bypass fraction of a cooling and dehumidifying coil
Humid air crossing a coil may leave warmer and wetter than air in equilibrium with the coldest effective surface. A common reduced model treats a fraction \(b\) of the dry-air stream as bypassing the surface while the remainder reaches a saturated state at the apparatus dew-point temperature. Consider a steady coil at nearly constant total pressure, neglect fan work and heat gains, and use dry-air mass as the conserved basis. Denote inlet, saturated-surface and mixed outlet states by \(i,s,o\), with humidity ratio \(\omega\) and moist-air enthalpy \(h\) per kilogram of dry air.
Water-vapour and mixed-stream enthalpy balances give two independent ways to estimate the same bypass fraction:
Solving either for \(b\) exposes a consistency check on measured data and the assumed single surface state:
The condensed water remains a separate outlet from the coil. With condensate leaving at liquid enthalpy \(h_\ell\) in the same reference convention, an overall balance gives positive heat removal
The mixed-state model requires
It also requires incoming air wet enough for condensation on the assumed surface. A dry surface with solely sensible cooling cannot be represented by forcing a saturated leaving branch.
Worked example
Evaluate air and water leaving a coil
Change the inputs and test this calculation.
Use \(\omega_i=0.0160\), \(\omega_s=0.00760\) kg/kg dry air, \(h_i=71.0\), \(h_s=29.3\) kJ/kg dry air and \(b=0.250\). Then \(\omega_o=0.00970\) and \(h_o=39.7\) kJ/kg dry air. With \(1.20\) kg/s dry air, the condensate rate is \(0.00756\) kg/s. For \(h_\ell=42.0\) kJ/kg, heat removal is
Second application
Test whether three measurements share one apparatus dew point
Change the inputs and test this calculation.
On another run with the same inlet and assumed surface, measured outlet values are \(\omega_o=0.01096\) and \(h_o=41.8\) kJ/kg dry air. The humidity ratio implies \(b=0.400\), while enthalpy gives \(b=0.300\). At \(b=0.400\) the model would predict \(h_o=46.0\) kJ/kg. The \(4.2\) kJ/kg discrepancy indicates that measurement uncertainty, a more distributed surface temperature or another heat transfer must be considered before inferring a unique bypass fraction.
Try it · Coil bypass
Set the inputs to the values in the worked example, then vary one quantity while holding the others fixed. Compare the curve and numerical balance with the second application. The calculation uses the assumptions derived above; its readout identifies bounds such as choking, phase-region changes and inconsistent measurements.
Choose a quantity that survives condensation
A ventilation duct can carry an unchanged mass flow of dry air while water evaporates into it or condenses out. It is therefore convenient to express water content and mixture energy per kilogram of dry air. Model the dry air and water vapour as ideal gases sharing a common temperature and total volume. The partial pressure of each gas is the pressure it would exert if it occupied this volume alone. Dalton’s law gives
Relative humidity \(\phi=p_v/p_{\rm sat}(T)\) describes proximity to saturation at the current temperature. It is not the mass fraction of water. For humidity ratio \(w=m_v/m_a\), divide the two ideal-gas mass equations. The common temperature and volume cancel, leaving a ratio of molar masses multiplied by the partial-pressure ratio.
Before any water condenses during cooling at constant total pressure, the humidity ratio and vapour partial pressure remain fixed. Relative humidity rises because saturation pressure falls. The dew point is the temperature at which saturation pressure equals that fixed vapour pressure. Once that point is crossed, further cooling can remove water.
Find water removal and the associated cooling duty
Air enters a coil at 30 °C, 100 kPa and 60% relative humidity, and leaves saturated at 12 °C. Use \(p_{\rm sat}(30)=4.24\) kPa and \(p_{\rm sat}(12)=1.40\) kPa. The inlet vapour partial pressure is 2.544 kPa, giving \(w_1=0.01624\) kg water per kg dry air. The outlet ratio is \(w_2=0.00883\). For dry-air flow 0.50 kg/s the condensate flow is \(0.50(0.01624-0.00883)=0.00371\,\mathrm{kg/s}\), about 13.3 kg/h.
Using a 0 °C liquid-water reference, approximate moist-air enthalpy per kilogram dry air by \(h=1.005T+w(2501+1.86T)\) kJ/kg dry air with \(T\) in °C. The duct streams carry about 71.7 and 34.3 kJ/kg dry air. Condensate leaving at 12 °C carries \(h_l\simeq4.18(12)=50.2\,\mathrm{kJ/kg}\). Energy conservation gives heat removed per kilogram dry air as \(h_1-h_2-(w_1-w_2)h_l\), approximately 37.0 kJ/kg dry air, or 18.5 kW.
Separate humidity ratio from relative humidity
Suppose the outlet stream is reheated to 20 °C without adding water. Its vapour pressure remains 1.40 kPa at the same total pressure. Since \(p_{\rm sat}(20)=2.34\,\mathrm{kPa}\), the new relative humidity is 59.8%. Neither evaporating water nor drying the air was required during this reheat. A sensor reporting 60% at both the inlet and reheated outlet therefore describes two air streams containing rather different masses of water. The coil water balance, written on the dry-air basis, explains the apparent coincidence.
Bracket an unknown dew point
At the original inlet the vapour pressure was 2.544 kPa. Suppose a saturation table gives 2.487 kPa at 21 °C and 2.644 kPa at 22 °C. Linear interpolation over this short interval puts the dew point at \(21+(2.544-2.487)/(2.644-2.487)=21.36^\circ\mathrm C\). A coil surface warmer than this value cannot start condensing the entering air locally under the stated conditions.
Balance an adiabatic spray chamber
A direct evaporative cooler behaves differently from a refrigerated cooling coil. Water is added to an airstream, the dry-bulb temperature falls, and the humidity ratio increases. Assume steady operation, negligible shaft work and heat leakage, unchanged total pressure, and no liquid droplets carried out. Express enthalpy per kilogram dry air. The dry-air flow is conserved; added liquid flow per kilogram dry air equals \(w_2-w_1\). The resulting energy balance is
Use the same enthalpy reference for liquid and moist air. If the added water has low liquid enthalpy on that reference, the moist-air enthalpy is approximately constant. Often the recirculated liquid is near the leaving-air temperature; the more accurate energy equation above can be used without that approximation. An ideal infinitely long saturated contactor has \(\phi_2=1\), but a finite cooler generally leaves unsaturated air. An outlet temperature or a contact effectiveness is needed in addition to the balances unless saturation is specified.
With constant heat capacities one may write \(h_2=c_{pa}T_2+w_2(h_{g0}+c_{pv}T_2)\). Substituting this form into the balance and grouping the unknown \(w_2\) shows explicitly which measured quantities are needed. The process cannot cool below the adiabatic saturation limit for the given inlet state and water supply merely by increasing the spray rate.
Check outlet humidity and water consumption
A cooler receives air at 35 °C and 100 kPa with inlet humidity ratio 0.0080 kg/kg dry air and dry-air flow 0.60 kg/s. Its measured outlet temperature is 23 °C and liquid makeup enters at 20 °C. Use \(h=1.005T+w(2501+1.86T)\) kJ/kg dry air and \(h_\ell=4.18T\) kJ/kg. The inlet carries \(1.005(35)+0.008[2501+1.86(35)]=55.70\,\mathrm{kJ/kg}\) dry air; liquid enters with \(h_\ell=83.6\,\mathrm{kJ/kg}\).
The outlet equation is \(55.70+(w_2-0.0080)83.6=1.005(23)+w_2[2501+1.86(23)]\), giving \(w_2=0.01297\,\mathrm{kg/kg}\) dry air. Thus liquid consumption is \(0.60(0.01297-0.0080)=0.00298\,\mathrm{kg/s}\), or about 10.7 kg/h. The outlet vapour pressure is
At a supplied saturation pressure of 2.81 kPa for 23 °C, this corresponds to about 73% relative humidity, consistent with a finite contact process.
Treating air as a dry sensible stream would suggest a cooling duty of roughly \(0.60(1.005)(35-23)=7.24\,\mathrm{kW}\) removed from the cabinet. In this adiabatic device most of the sensible decrease supplies evaporation inside the boundary; no corresponding cooling-coil duty exists. A downstream process sensitive to water content may therefore react very differently to evaporative cooling and cooling plus dehumidification, even when both report the same outlet dry-bulb temperature.
An independent check can be made by weighing the makeup reservoir over a stable ten-minute test. At the predicted consumption it should lose about \(10.7/6=1.78\) kg, provided no liquid is stored in the spray circuit during that interval. A greater measured loss together with the same outlet humidity suggests entrained droplets, drainage or leakage rather than necessarily more evaporation. A humidity probe downstream of an effective droplet separator and a separate liquid-drain measurement distinguish those paths and make the water balance close.
Identify condensation from a humidity-ratio chart
At a total pressure of 101.325 kPa,
The plot uses the Buck saturation-pressure correlation over liquid water. Follow a sealed parcel cooled at constant pressure with no condensation until it reaches saturation.

Read values from the plot
| Dry-bulb temperature (°C) | Relative humidity 35% | Relative humidity 65% | Relative humidity 100% |
|---|---|---|---|
| 5 | 1.8801 | 3.5006 | 5.402 |
| 15 | 3.6852 | 6.8789 | 10.646 |
| 25 | 6.8828 | 12.905 | 20.078 |
| 35 | 12.328 | 23.291 | 36.57 |
| 45 | 21.315 | 40.783 | 65.039 |
Interactive calculation · change the inputs of this example
Choose an initial temperature and relative humidity, then follow the horizontal parcel-water line to saturation.
The curves below are recalculated from this section’s equations in your browser. The fixed reference plot above remains available for comparison.