"""OneSimulation example: three stirred tank reactors in series under feedback control.
Requires the installed, activated OneSimulation runtime.

A controller adjusts the inlet concentration of the first of three tank reactors so that the
outlet of the third follows a set point. Proportional control is compared with the exact
closed-loop step response and the classical stability limit of three lags; a Ziegler-Nichols PI
controller then removes the offset.
"""

# # Tank series with feedback control
#
# Three equal, perfectly mixed tanks of volume $V$ are connected in series with the flow $q$. In
# each tank the reactant decays by a first-order reaction $A\to B$ with the rate constant $k$:
#
# $$V\,\frac{dc_i}{dt} = q\,(c_{i-1}-c_i) - k\,V\,c_i
#   \quad\Longleftrightarrow\quad
#   \tau\,\frac{dc_i}{dt} = G\,c_{i-1}-c_i,\qquad \tau=\frac{V}{q+kV},\quad G=\frac{q}{q+kV},$$
#
# so every tank is a first-order lag with time constant $\tau$ and static gain $G<1$. A feedback
# controller measures the outlet $c_3$ and sets the inlet concentration $c_0$ of the first tank,
# for instance by dosing a concentrate into the feed.
#
# | block | law | value |
# |---|---|---|
# | tank $i$ | $\tau\dot c_i = G c_{i-1} - c_i$ | $V=2$ m³, $q=0.01$ m³/s, $k=0.005$ 1/s |
# | controller | $c_0 = K_p e + K_i\int e\,dt$, $\;e=c_\text{set}-c_3$ | $0 \le c_0 \le 20$ mol/m³ |
#
# The loop is integrated as a signal-flow graph with the classical Runge-Kutta method.
#
# **Reference.** With proportional control the closed loop has the transfer function
# $K_pG^3/\big((\tau s+1)^3+K_pG^3\big)$; its step response is computed independently by
# `scipy.signal`, and its steady offset is $c_\text{set}/(1+K_pG^3)$. The Routh criterion gives
# the ultimate gain $K_u = 8/G^3$, at which the loop oscillates with the period
# $P_u = 2\pi\tau/\sqrt3$ (Seborg, Edgar, Mellichamp & Doyle, *Process Dynamics and Control*,
# chapter 11). Ziegler & Nichols (*Trans. ASME* 64, 1942) tune a PI controller from these two
# numbers: $K_p = 0.45\,K_u$, $T_i = P_u/1.2$.

import numpy as np
from onesim.physics.systems import (
    ControlSignalFlowConfiguration,
    ControlSignalFlowPublicApi,
    SignalBlock,
)
from onesim.visualization import plots, theme
from scipy import signal

theme.set()


# ## Plant data
#
# The three tank parameters give the time constant and gain of each lag, and from them the
# stability limit of the loop.

volume, flow, rate, setpoint = 2.0, 0.01, 0.005, 1.0
tau, G = volume / (flow + rate * volume), flow / (flow + rate * volume)
ultimate_gain, ultimate_period = 8 / G**3, 2 * np.pi * tau / np.sqrt(3)
print(
    f"tank time constant {tau:.1f} s, tank gain {G:.3f}; ultimate gain {ultimate_gain:.1f}, ultimate period {ultimate_period:.1f} s"
)


# ## Proportional control
#
# The plant is one tuple of blocks, shared by all runs. The tanks start empty and the set point
# is 1 mol/m³. Four controller gains between a quarter of
# the ultimate gain and 10 % above it; the inlet concentration is not limited in these runs.

plant = (
    SignalBlock("dose", "gain", inputs=("controller",), parameters={"gain": G}),
    SignalBlock(
        "tank1", "first_order", inputs=("dose",), parameters={"time_constant": tau}
    ),
    SignalBlock("into2", "gain", inputs=("tank1",), parameters={"gain": G}),
    SignalBlock(
        "tank2", "first_order", inputs=("into2",), parameters={"time_constant": tau}
    ),
    SignalBlock("into3", "gain", inputs=("tank2",), parameters={"gain": G}),
    SignalBlock(
        "tank3", "first_order", inputs=("into3",), parameters={"time_constant": tau}
    ),
    SignalBlock(
        "error",
        "sum",
        inputs=("setpoint", "tank3"),
        parameters={"weights": (1.0, -1.0)},
    ),
)
fractions = (0.25, 0.5, 0.95, 1.05)
loop = lambda K: signal.lti(
    [K * G**3],
    np.polyadd(np.polymul(np.polymul([tau, 1], [tau, 1]), [tau, 1]), [K * G**3]),
)
proportional = {
    f: ControlSignalFlowPublicApi().run(
        ControlSignalFlowConfiguration(
            parameters=dict(
                blocks=plant
                + (
                    SignalBlock("setpoint", "constant", parameters={"value": setpoint}),
                    SignalBlock(
                        "controller",
                        "pid",
                        inputs=("error",),
                        parameters={"proportional_gain": f * ultimate_gain},
                    ),
                ),
                final_time=4000.0,
                time_step=1.0,
            )
        )
    )
    for f in fractions
}

for f, run in proportional.items():
    K = f * ultimate_gain
    exact = setpoint * signal.step(loop(K), T=run.times)[1]
    outlet = np.asarray(run.signals["tank3"])
    print(
        f"Kp = {f:4.2f} Ku: largest deviation from the exact step response {np.max(np.abs(outlet - exact)):.1e} mol/m^3"
        + (
            f", offset {setpoint - outlet[-1]:.5f} (exact {setpoint / (1 + K * G**3):.5f})"
            if f < 0.9
            else ""
        )
    )
for f in (0.95, 1.05):
    times, outlet = np.asarray(proportional[f].times), np.asarray(
        proportional[f].signals["tank3"]
    )
    peaks = times[1:-1][(outlet[1:-1] > outlet[:-2]) & (outlet[1:-1] > outlet[2:])]
    print(
        f"Kp = {f:4.2f} Ku: oscillation period {np.diff(peaks).mean():.1f} s, from the closed-loop poles {2 * np.pi / loop(f * ultimate_gain).poles.imag.max():.1f} s "
        f"(ultimate period {ultimate_period:.1f} s)"
    )


# ## Ziegler-Nichols PI control
#
# The PI controller removes the offset. Its output is limited to the physical range of the inlet
# concentration, with back-calculation against integrator wind-up. After 4000 s the set point is
# raised to 1.5 mol/m³. The tuning aims at a quarter decay ratio, so the response rings before it settles.

Kp, Ti = 0.45 * ultimate_gain, ultimate_period / 1.2
pi_run = ControlSignalFlowPublicApi().run(
    ControlSignalFlowConfiguration(
        parameters=dict(
            blocks=plant
            + (
                SignalBlock(
                    "setpoint",
                    "source",
                    source=lambda t: setpoint if t < 4000 else 1.5 * setpoint,
                ),
                SignalBlock(
                    "controller",
                    "pid",
                    inputs=("error",),
                    parameters={
                        "proportional_gain": Kp,
                        "integral_gain": Kp / Ti,
                        "lower": 0.0,
                        "upper": 20.0,
                        "anti_windup": "back_calculation",
                        "tracking_time": Ti,
                    },
                ),
            ),
            final_time=8000.0,
            time_step=1.0,
            event_times=(4000.0,),
        )
    )
)
pi_times, pi_outlet = np.asarray(pi_run.times), np.asarray(pi_run.signals["tank3"])
print(
    f"PI controller Kp = {Kp:.2f}, Ti = {Ti:.1f} s: outlet at 4000 s {pi_outlet[pi_times <= 4000][-1]:.5f}, at 8000 s {pi_outlet[-1]:.5f} "
    f"(set points 1.0 and 1.5); highest inlet concentration {np.max(pi_run.signals['controller']):.2f} mol/m^3"
)


# ## Figure
#
# Outlet concentration under proportional control against the exact response (a quarter of,
# half of and 5 % above the ultimate gain), the PI controlled outlet, and the inlet concentration
# the PI controller sets.

fig = plots.figure(1, 3, size=(18, 5))
plots.line(
    points={
        f"Kp = {f} Ku": (
            np.asarray(run.times)[::40],
            np.asarray(run.signals["tank3"])[::40],
        )
        for f, run in proportional.items()
        if f != 0.95
    },
    reference={
        f"Kp = {f} Ku": (
            run.times,
            setpoint * signal.step(loop(f * ultimate_gain), T=run.times)[1],
        )
        for f, run in proportional.items()
        if f != 0.95
    },
    hlines={"set point": setpoint},
    xlimits=(0, 3000),
    ylimits=(-0.3, 2.3),
    xlabel="time [s]",
    ylabel="outlet concentration c3 [mol/m3]",
    title="Proportional control, dashed: exact",
    legend="upper left",
    ax=fig[0],
)
plots.line(
    y={"outlet c3": (pi_times, pi_run.signals["tank3"])},
    hlines={"set point": 1.0, "new set point": 1.5},
    xlabel="time [s]",
    ylabel="concentration [mol/m3]",
    title="Ziegler-Nichols PI control",
    legend="lower right",
    ax=fig[1],
)
plots.line(
    y={"inlet concentration c0": (pi_times, pi_run.signals["controller"])},
    xlabel="time [s]",
    ylabel="inlet concentration [mol/m3]",
    title="Controller output (limited to 20 mol/m3)",
    ax=fig[2],
)
plots.show()


# ## Going further
#
# Add a transport delay between the controller and the first tank and watch the ultimate gain
# drop. Replace the PI controller by a sampled one (`sample_hold`) to see the effect of a slow
# analyser, or make the reaction rate in the tanks drift and test how robust the tuning is.